Fault ride through project
-
Decision paper on generation fault ride through
15 Nov 2016
We have decided to amend the Code to include fault ride through standards for generating units.
The key elements of the standards are:
- generators connected to a network must ensure their assets remain stable and connected within defined over and under voltage no-trip zones during and immediately after a.c. transmission faults
- generators must ensure their assets remain stable and connected within a defined over voltage no-trip zone during and immediately after faults on the high voltage direct current (HVDC) link
- generators must ensure their assets generate reactive current to oppose changes in voltage that occur during and immediately after a.c. transmission faults.
The Code amendment will deliver long-term benefits to consumers by contributing to the reliable supply of electricity to consumers and improving the efficient operation of the electricity industry.
We have published the Gazette notice, a paper outlining the reasons for this decision and a summary of the submissions received. The amendment will come into force on 24 November 2016.
-
Download a ZIP file containing all documents
-
Decision Paper
Decision-Paper.pdf (PDF, 205 KB)
Last updated: 15 November 2016
-
Summary of Submissions
Summary-of-Submissions.pdf (PDF, 185 KB)
Last updated: 15 November 2016
-
Gazette notice
Gazette-Notice-EIPCA-Generation-Fault-Ride-Through-2016.pdf (PDF, 23 KB)
Last updated: 27 October 2016
-
Code amendment parts 1, 8
EIPCA-Generation-Fault-Ride-Through-2016.pdf (PDF, 1.2 MB)
Last updated: 27 October 2016
-
Stage 2 - Power System studies/Recommendations
May 2010
Stage 2 involves power system studies to determine current and future system performance, and analysis of material presented in stage 1 in order to determine a suitable Fault Ride Through envelope that will provide a requirement for generators wishing to connect to the power system.
-
Generator Fault Ride Through Investigation - Stage 2 Report
Gen-fault-ride-through-stage2.pdf (PDF, 4.9 MB)
Last updated: 19 August 2016
-
-
Stage 1 - Literature Review/Data Collection
Feb 2009
Stage 1 reviews existing grid planning criteria, protection requirements, previous ride through studies, international standards and the ability of generators to meet Voltage Ride Through criteria.
-
Generator Fault Ride Through (FRT) Investigation Stage 1: Literature Review
GEN-FRT-Stage1-Lit-review.pdf (PDF, 1 MB)
Last updated: 21 August 2016
-